DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/25/2021        Last Data Refresh: 04/24/2021        Report Generated from DOPPLER
 
Facility ID: 8629857
Facility Name: FRANKLINS BAIT & TACKLE
 
10/30/2020 Editable Letter Activity Burgess, Torie Anne
Activity Title: Compliance Assistance Offer Letter Activity Status: Open
10/28/2020 Site Inspection Activity Closed Burgess, Torie Anne
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 10/28/2020
Activity Closed Date: 10/30/2020 Activity Closed By: BURGESS_TA_1
Events:
Event Type: Activity has been finished Date: 10/30/2020
Comment: Finished
02/25/2019 Editable Letter Activity Burgess, Torie Anne
Activity Title: Compliance Assistance Offer Letter Activity Status: Open
02/21/2019 Site Inspection Activity Closed Burgess, Torie Anne
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/21/2019
Activity Closed Date: 02/25/2019 Activity Closed By: BURGESS_TA_1
Events:
Event Type: Activity has been finished Date: 02/25/2019
Comment: Finished
10/23/2018 Site Inspection Activity Closed French, Edwin C.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 10/23/2018
Activity Closed Date: 10/25/2018 Activity Closed By: FRENCH_EC_1
Events:
Event Type: Activity has been finished Date: 10/25/2018
Comment: Finished
Attachments:
Attachment Date: 10/25/2018 User: FRENCH_EC_1
Description: Hurricane Michael Questionnaire
View Attachment
09/21/2016 Editable Letter Activity Hodges, Zachary L.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 09/21/2016
Comment: Finished
Attachments:
Attachment Date: 09/21/2016 User: HODGES_ZL_1
Description: NCL 9.21.16
View Attachment
09/20/2016 Site Inspection Activity Closed Hodges, Zachary L.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 09/19/2016
Activity Closed Date: 09/21/2016 Activity Closed By: HODGES_ZL_1
Events:
Event Type: Activity has been finished Date: 09/21/2016
Comment: Finished
03/27/2015 Site Inspection Activity Closed Hodges, Zachary L.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 03/27/2015
Activity Closed Date: 03/27/2015 Activity Closed By: HODGES_ZL_1
Events:
Event Type: Activity has been finished Date: 03/27/2015
Comment: Finished
03/27/2015 Editable Letter Activity Hodges, Zachary L.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/22/2016
Comment: Finished
Attachments:
Attachment Date: 02/22/2016 User: HODGES_ZL_1
Description: NCL 3.27.15
View Attachment
12/23/2010 Site Inspection Activity Closed Krazit, Jason L.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 12/23/2010
Activity Closed Date: 12/23/2010 Activity Closed By: KRAZIT_JL_1
Events:
Event Type: Activity has been finished Date: 12/23/2010
Comment: Finished
12/23/2010 Emergency Preparedness Information Activity Krazit, Jason L.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/23/2010
Events:
Event Type: Activity has been finished Date: 12/23/2010
Comment: Finished
12/23/2010 Editable Letter Activity Krazit, Jason L.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 12/23/2010
Comment: Finished
Events:
Event Type: Document has been sent Date: 12/23/2010
Comment: Sent on Thu Dec 23 00:00:00 EST 2010
Attachments:
Attachment Date: 12/23/2010 User: KRAZIT_JL_1
Description: NCL
View Attachment
01/29/2010 Violation Open Krazit, Jason L.
Significance: SNC-B Status: Open
Criteria ID: 1132
Rule: 62-761.800(2)(b)
Comments: Unmaintained systems are defined in Rule definition #71 as: "a storage tank system that was not closed in accordance with Department rules"; or, "an out-of-service tank system that was not returned to service within the 2, 5 or 10 year period." Note that a system can be out-of-service for 1, 2, 5 or 10 years before becoming unmaintained, and should be in compliance if out-of-service requirements are met. Unmaintained systems are not in violation until after being unmaintained for more than 90 days without closure or being returned to service. This item also covers tank systems found on a piece of property that were not previously registered. Document all time frames discussed with the facility owner/operator. See Rule definition #13 "Discovery"
01/29/2010 Editable Letter Activity Krazit, Jason L.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/29/2010
Comment: Finished
Attachments:
Attachment Date: 01/29/2010 User: KRAZIT_JL_1
Description: NCL
View Attachment
01/29/2010 Site Inspection Activity Closed Krazit, Jason L.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 01/29/2010
Activity Closed Date: 01/29/2010 Activity Closed By: KRAZIT_JL_1
Events:
Event Type: Activity has been finished Date: 01/29/2010
Comment: Finished
09/23/2008 Site Inspection Activity Closed Henderson, Sylvia A.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 09/23/2008
Activity Closed Date: 09/23/2008 Activity Closed By: HENDERSON_SA_1
Comments:
Comment Date: 08/04/2008 User: HENDERSON_SA_1
Description: RD: Visual Sump & dispensers SIRS, cathodic protection, acrificial anode cp, MECHANICAL LINE LEAK DETECTIOPN
09/23/2008 Editable Letter Activity Henderson, Sylvia A.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Comments:
Comment Date: 10/23/2008 User: HENDERSON_SA_1
Description: Lining - APT Dispenser Liners- Environ
06/04/2008 Attachment Henderson, Sylvia A.
06/04/2008 Editable Letter Activity Henderson, Sylvia A.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Comments:
Comment Date: 08/04/2008 User: HENDERSON_SA_1
Description: 1. Must remove strom water and product as not to contaminate the soil or groundwater 2. Must provide financial responsibility/insurance 3. Must provide visuals monitoring - recordkeeping 4. Must provide this information within 5 days to this office fax to 850 875-9215 5 A reinspection will be conducted.
06/04/2008 Site Inspection Activity Closed Henderson, Sylvia A.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/04/2008
Activity Closed Date: 06/04/2008 Activity Closed By: HENDERSON_SA_1
Comments:
Comment Date: 06/26/2007 User: KRAZIT_JL_1
Description: Release detection is monthly visuals. Piping above ground. Recommend removing leaves from secondary containment.
06/04/2008 Violation Open Henderson, Sylvia A.
Significance: Minor Status: Open
Criteria ID: 2159
Rule: 62-762.821(2)(b)4.
Comments: Facility must provide documentation (invoices, work orders) that the system defect has been repaired. These invoices will typically describe the problem, and how the repair was made. If it can not or will not be repaired, was the system closed?
Comments:
Comment Date: 08/04/2008 User: HENDERSON_SA_1
Description: 60 psi 12,000 dual compartmentd gass, 4,00 Gall diesel AST Hydro Passed no leaks
06/04/2008 Violation Open Henderson, Sylvia A.
Significance: SNC-B Status: Open
Criteria ID: 2089
Rule: 62-762.611(2)(b)
Comments: Mark this as out of compliance if the facility is not performing visual inspections or is not recording the results monthly. Walk around and look at the tank, containment, all system components, valve and hydrant pits if applicable, and piping. Record your observations. Review monthly records. Does the physical evidence support the facility written record? Look for evidence of wetting, discoloration, blistering, corrosion, cracks, structural damage, and leakage. Examine the tank, saddle, containment inner and outer walls, containment floors, dike height. Note that this applies to all visible parts of an AST system. This rule and 762.611(2)(a)2 deals with release detection for Category-A and B ASTs only. Rule 762.611(1)(b) covers release detection for Category-C systems. Rules 762.611(3)(a)1, 762.611(3)(a)2, 762.611(3)(b), 762.611(3)(c), 762.611(3)(d)1 and 762.611(3)(d)2 deal with all piping release detection.
Comments:
Comment Date: 08/04/2008 User: HENDERSON_SA_1
Description: Installing 4,000; 12,000 gallon AST.
06/04/2008 Violation Open Henderson, Sylvia A.
Significance: Minor Status: Open
Criteria ID: 1124
Rule: 62-761.710(3)(a), 62-761.710(3)(b), 62-761.710(3)(c), 62-761.710(3)(d), 62-761.710(3)(e), 62-761.710(3)(f), 62-761.710(3)(g), 62-761.710(3)(h)
Comments: The Rule cites does not list routine operation and maintenance records. If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. Periodic inspections and tank system measurements - rules 62-761.610(3)(a)1, 62-761.700(4)-(5) & 62-761.700(6) b. Supporting claims for equipment in use at facility. - rule 62-761.600(1)(a)3 c. History of what has been done at facility - see 62-761.500 rules. d. Cathodic protection system history - rules 62-761.500(1)(e)1 & 62-761500(1)(e)3 e. Site suitability determination - this document must be updated when site conditions change- rule 62-761.600(1)(f) f. Vapor monitoring plan - this document must be updated annually - rule 62-761.600(1)(g) g. Closure reports - rule 62-761.800(3)(d) h. Single check valve - PSSC documentation that no other buried valves exist - rule 62-761.610(3)(a)1
Comments:
Comment Date: 08/01/2008 User: HENDERSON_SA_1
Description: Less Than 1/2" of product and or water in fill port
06/04/2008 Violation Open Henderson, Sylvia A.
Significance: Minor Status: Open
Criteria ID: 1122
Rule: 62-761.710(1)
Comments: Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period.
Comments:
Comment Date: 07/31/2008 User: HENDERSON_SA_1
Description: See Annual Compliance Letter for attachments
06/04/2008 Violation Closed Henderson, Sylvia A.
Significance: Minor Status: Closed
Criteria ID: 1002
Rule: 62-761.400(2)(a)
Comments: Does STCM accurately reflect the tanks at the facility? This question concerns the registration process and payment of fees only - it is not about accurate registration. Check the number of tanks listed on the registration placard. Can the facility owner/operator produce a registration form to document submittal to DEP? Does STCM show that all DEP fees are paid? At the time of tank closure, a registration form should be submitted showing the change in tank codes.
Comments:
Comment Date: 07/31/2008 User: HENDERSON_SA_1
Description: Release detection not performed at least once a month. Please provide for the period covering 11/08/2007
06/04/2008 Violation Closed Henderson, Sylvia A.
Significance: SNC-B Status: Closed
Criteria ID: 1004
Rule: 62-761.400(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2).
Comments:
Comment Date: 07/31/2008 User: HENDERSON_SA_1
Description: Recommend: Removal of all foliage/grass and objects adjacent tanks. Please allow a clear view of the secondary containment wall to ensure observation for leaks and containment wall breaches.
06/04/2008 Violation Open Henderson, Sylvia A.
Significance: Minor Status: Open
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
Comments:
Comment Date: 08/01/2008 User: HENDERSON_SA_1
Description: Southside One Stop has had Major out of compliance, non-compliance leters issued for 20080731 and 20071108. Please review out of compliance photos for numerous violations.
06/04/2008 Attachment Henderson, Sylvia A.
12/26/2007 Issue Document Activity Gillman, Mark
Activity Status: Closed
Contact Name: Denise Franklin Activity Closed Date: 12/26/2007
07/02/2007 Enforcement Tracking Activity Gillman, Mark
Activity Status: Open
Comments:
Comment Date: 07/27/2007 User: GILLMAN_M
Description: Accepted.
12/22/2006 Enforcement Referral Activity - OLD Activity Krazit, Jason L.
No data found!
12/21/2006 Enforcement Referral Activity Krazit, Jason L.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 07/02/2007
Events:
Event Type: Activity/Document was accepted on this date Date: 07/02/2007
Comment: Possible Indigent Consent Order Case. The District is waiting for financial analysis from Tallahassee.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 07/02/2007
Comment: Recieved and aknowledged.
Events:
Event Type: Activity has been submitted for approval Date: 12/22/2006
Comment: Franklins Bait and Tackle is not doing business and is for sale. Mrs. Franklin said she cant afford insurance or tank removal. She doesnt have her placard,records, test, insurance. She did have the tanks pumped and each one has less than 1" of product.
12/20/2006 Violation Open Krazit, Jason L.
Significance: SNC-B Status: Open
Criteria ID: 1004
Rule: 62-761.400(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2).
Comments:
Comment Date: 06/25/2007 User: KRAZIT_JL_1
Description: Store closed at time of inspection for upgrade.
12/20/2006 Editable Letter Activity Krazit, Jason L.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 12/20/2006
Comment: Sent on Wed Dec 20 00:00:00 EST 2006
Comments:
Comment Date: 06/27/2007 User: KRAZIT_JL_1
Description: Release detection is visuals of tank and dispensers. All piping is above ground.
Attachments:
Attachment Date: 12/20/2006 User: KRAZIT_JL_1
Description: NCL Report
View Attachment
12/20/2006 Violation Open Krazit, Jason L.
Significance: Minor Status: Open
Criteria ID: 1128
Rule: 62-761.800(1)(c)
Comments: Know the start date of the out-of-service period, and document it. Keep track of the time period and advise the facility owner/operator of approaching deadline. Note: Rule definition #40 includes in the definition of "out-of-service - ten years for storage tank systems with secondary containment".
Comments:
Comment Date: 06/25/2007 User: KRAZIT_JL_1
Description: Release detection is veeder root TLS-350, monthly visuals and LLD. Piping is double wall.
12/20/2006 Violation Open Krazit, Jason L.
Significance: Minor Status: Open
Criteria ID: 1003
Rule: 62-761.400(2)(f)
Comments: All federal facilities with USTs will have a placard. Per FS 376.3077, "It is unlawful for any owner, operator, or supplier to pump or otherwise deposit any motor fuel into a tank required to be registered under section 376.303 FS, unless proof of valid registration is displayed on such tank itself or the dispensing or measuring device connected thereto or, where appropriate, in the office or kiosk of the facility where the tank is located." Penalties can be assessed to the facility owner for failure to properly register tank systems. Note that penalties can be assessed to the supplier that delivers motor fuel to an unregistered facility. Check the details on the placard. Do they agree with the location you are inspecting? Owners of multiple facilities may switch placards by mistake. Placards are not always issued or received in a timely manner at the change of year period (June and July). Provide the DEP Tallahassee phone number to the facility so they may resolve problems (850) 245-8850; (850) 245-8840. Check STCM in the registration/placard section for the date that the payment was made and the date that the placard was issued. The location of the placard in plain view can be subjective in interpretation: a. For vehicular fuel facilities, plain view is meant to allow the transport delivery driver to view the placard prior to delivering fuel. b. A legal definition is an exception to the general requirement of a valid search warrant to legitimize a search or seizure; a search implies prying into hidden places, and it is not a search to observe what is open to view.
Comments:
Comment Date: 06/25/2007 User: KRAZIT_JL_1
Description: Abandoned tanks. Cannot reach owners. Less than 1" of product in both UST's.
12/20/2006 Violation Open Krazit, Jason L.
Significance: Minor Status: Open
Criteria ID: 1002
Rule: 62-761.400(2)(a)
Comments: Does STCM accurately reflect the tanks at the facility? This question concerns the registration process and payment of fees only - it is not about accurate registration. Check the number of tanks listed on the registration placard. Can the facility owner/operator produce a registration form to document submittal to DEP? Does STCM show that all DEP fees are paid? At the time of tank closure, a registration form should be submitted showing the change in tank codes.
Comments:
Comment Date: 06/25/2007 User: KRAZIT_JL_1
Description: Release detection is monthly visuals, ATG-Gilbarco EMC, Line leak detector. Piping is DW fiberglass. Godfrey Dickson performed inspection but never closed.
12/19/2006 Site Inspection Activity Closed Krazit, Jason L.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 12/19/2006
Activity Closed Date: 12/20/2006 Activity Closed By: KRAZIT_JL_1
Comments:
Comment Date: 06/24/2007 User: KRAZIT_JL_1
Description: Release dection is Gilbarco ATG,Visuals and line leak detecter. Piping for underground is fiberglass, above ground is galvanized.
10/31/2005 Violation Open Unknown, User
Significance: Minor Status: Open
Criteria ID: 1125
Rule: 62-761.800(2)(a)1.a., 62-761.800(2)(a)1.b., 62-761.800(2)(a)1.c., 62-761.800(2)(a)1.d., 62-761.800(2)(a)3.
Comments: Per Rule definition #40, "Out-of-service" means a storage tank system that: (a) Is designated as an out-of-service system by owner or operator notification to the Department on Form 62-761.900(2), F.A.C.; (b) Is empty as defined in Rule 62-761.200(18), F.A.C. "Empty" means all regulated substances have been removed so that no more than one inch in depth or 0.3 percent by weight of total system capacity of regulated substances remains in the storage tank system.; and (c) Does not have regulated substances transferred into or withdrawn from the tank as specified in subsection 62-761.800(1), F.A.C., for a maximum time of: 1. Two years of being taken out-of-service for USTs; or 2. Ten years of being taken out-of-service for storage tank systems with secondary containment. If all of the above are not met, then consider the system as still in service status for enforcement purposes. Record discrepancies accordingly. Document the reason for placement in this status. Monitor the time limitations. Verify that the tank has been emptied. Have the tank stuck or check the gauging device. Systems with secondary containment need not perform monthly release detection.
10/31/2005 Legacy Activity Brooks, Addie
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/08/2005 Violation Closed Brooks, Addie
Significance: Minor Status: Closed
Rule: 761.820(1)(a),(b),(c)
Comments:
Comment Date: 08/17/2020 User: BECKER_GT_1
Description: OCEPD received testing documents for the new AST: Fill port hydro test; AST interstitial integrity test; Krueger interstitial leak gauge; Clock fuel level gauge.
03/08/2005 Legacy Activity Brooks, Addie
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
03/08/2005 Legacy Activity Brooks, Addie
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
10/26/2004 Violation Closed Brooks, Addie
Significance: Minor Status: Closed
Rule: 761.700(1)(c)3
Comments:
Comment Date: 01/21/2020 User: DASHTAKI_K_1
Description: See attached Liquid status print out from TLS-350. All Functions Normal.
10/26/2004 Legacy Activity Brooks, Addie
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/26/2004 Violation Closed Brooks, Addie
Significance: Minor Status: Closed
Rule: 761.640(1)(c)
Comments:
Comment Date: 01/21/2020 User: HATCHER_JD_1
Description: VISUAL INSPECTION: 1/21/2020 Placard: ok FR: ok CFR: ok Tank: ok Piping: ok Dispenser: Top mounted. Overfill: site gauge. Monthly Visuals: provided and current. Leak detection: Monthly visuals with manual interstice checks.
10/26/2004 Violation Closed Brooks, Addie
Significance: Minor Status: Closed
Rule: 761.600(5)
Comments:
Comment Date: 01/21/2020 User: SUAREZ_J
Description: A Petroleum Storage Tank Inspection was conducted on December 18, 2019, by Juliana Suarez-Mitnik and David Maloney, Environmental Specialists with the Florida Department of Environmental Protection (Department) and Carl Joseph, Building Manager with Broward County Facilities Management. The facility had one 6,000-gallon underground tank with double-wall piping connected to an emergency generator. The tank has a suction system. The piping sump was dry with some signs of rust, the boots were pulled back. The spill bucket is double wall, dry and no signs of rust. The tank is monitored by a Veeder-Root TLS 300C that monitors the interstice, and it has a sensor for overfill; however, there is no audible or visual alarm near the tank to let anyone know if the tank is filled to 95% capacity . The facility has a contract with Florida Metro to do the monthly inspections where they check the Veeder-Root sensors and visually inspect the piping sump and the spill bucket. All Paperwork has not been provided to the Department. The facility did not provide the Department with the annual operability test for the Veeder- Root; the facility has not designated a specific overfill protection. the facility did not provide the Department with the integrity test for the piping sump and the spill bucket. The Facility has a designated person as an operator A and B, however, the facility has not provided the name of the C certified operator to the Department. The Department recommends cleaning, sealing ad painting any components beginning to show signs of rust, corrosion. Facility Contact information Carl Joseph, Building Manager Public Works Department, Facilities Management Division Office: (954) 357-6480 Cell: (954) 214-4880 CARLJOSEPH@broward.org The inspection report will be emailed to Freddy Ulloa, along with the Compliance Assistance Letter.
10/09/2003 Violation Closed Brock, Melissa
Significance: Minor Status: Closed
Rule: 700(1)(b)2a
Comments:
Comment Date: 02/28/2018 User: JARRETT_SE_1
Description: Dispenser #3 checked for leakage on the left side. Possible minor seepage still occurring but could not verify at the time of the inspection; recommend closely monitoring during the monthly release detection inspections.
10/09/2003 Legacy Activity Brock, Melissa
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
10/09/2003 Legacy Activity Brock, Melissa
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/09/2003 Violation Closed Brock, Melissa
Significance: Minor Status: Closed
Rule: 600(2)(d)
Comments:
Comment Date: 02/28/2018 User: PAYNE_CL_1
Description: Received DRF stating that closure assessment during spill bucket replacement activities included the collection of one laboratory soil sample at each spill bucket area. Laboratory analytical data for the RUL spill bucket soil sample indicated a Chapter 62-777, FAC Table II exceedance.
10/01/2002 Legacy Activity Brock, Melissa
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
11/06/2001 Legacy Activity Brock, Melissa
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
11/30/2000 Legacy Activity Brock, Melissa
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
11/28/2000 Violation Closed Brock, Melissa
Significance: Minor Status: Closed
Rule: 640(2)(c)4
Comments:
Comment Date: 04/26/2012 User: CRAFT_TT_1
Description: 2012.04.23 - Received BOI test results (passed).
11/28/2000 Legacy Activity Brock, Melissa
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
11/28/2000 Violation Closed Brock, Melissa
Significance: Minor Status: Closed
Rule: 640(1)(c)
Comments:
Comment Date: 04/26/2012 User: OWENS_JS_1
Description: Tanks installed in 1988 - no BOI required - recommended BUT not required.
11/28/2000 Violation Closed Brock, Melissa
Significance: Minor Status: Closed
Rule: 700(1)(c)1
Comments:
Comment Date: 04/26/2012 User: OWENS_JS_1
Description: Breach of Integrity test due next January 2013 - every 5 years - last tested 1/2008.
05/15/2000 Legacy Activity Unknown, User
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
11/30/1999 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 510(2)(d)
Comments:
Comment Date: 11/30/2010 User: COOK_JH_1
Description: Single-walled steel UST -- Modern Welding model AB-50, compartmented 4000/2000. Single-walled steel integral piping. Sacrificial anode CP. Removed with all components August 2010.
11/30/1999 Legacy Activity Unknown, User
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
11/30/1999 Violation Closed Unknown, User
Significance: SNC-B Status: Closed
Rule: 610(4)(a)1
11/30/1999 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 700(1)(b)1
Comments:
Comment Date: 11/30/2010 User: WINN_JP_1
Description: Containment has been sealed, although apparently with a material not included on the approved equipment list. Violation remains open.
09/30/1998 Legacy Activity Unknown, User