Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
| Journal Report | |||||||||||
| Report Run Date: 04/25/2021 Last Data Refresh: 04/24/2021 Report Generated from DOPPLER | |||||||||||
| Facility ID: | 8629857 | ||||||||||
| Facility Name: | FRANKLINS BAIT & TACKLE | ||||||||||
| 10/30/2020 | Editable Letter Activity | Burgess, Torie Anne | |||||||||
| Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Open | ||||||||
| 10/28/2020 | Site Inspection Activity Closed | Burgess, Torie Anne | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 10/28/2020 | ||||||||||
| Activity Closed Date: | 10/30/2020 | Activity Closed By: | BURGESS_TA_1 | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 10/30/2020 | ||||||||
| Comment: | Finished | ||||||||||
| 02/25/2019 | Editable Letter Activity | Burgess, Torie Anne | |||||||||
| Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Open | ||||||||
| 02/21/2019 | Site Inspection Activity Closed | Burgess, Torie Anne | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 02/21/2019 | ||||||||||
| Activity Closed Date: | 02/25/2019 | Activity Closed By: | BURGESS_TA_1 | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 02/25/2019 | ||||||||
| Comment: | Finished | ||||||||||
| 10/23/2018 | Site Inspection Activity Closed | French, Edwin C. | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 10/23/2018 | ||||||||||
| Activity Closed Date: | 10/25/2018 | Activity Closed By: | FRENCH_EC_1 | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 10/25/2018 | ||||||||
| Comment: | Finished | ||||||||||
| Attachments: | |||||||||||
| Attachment Date: | 10/25/2018 | User: | FRENCH_EC_1 | ||||||||
| Description: | Hurricane Michael Questionnaire | ||||||||||
| View Attachment | |||||||||||
| 09/21/2016 | Editable Letter Activity | Hodges, Zachary L. | |||||||||
| Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 09/21/2016 | ||||||||
| Comment: | Finished | ||||||||||
| Attachments: | |||||||||||
| Attachment Date: | 09/21/2016 | User: | HODGES_ZL_1 | ||||||||
| Description: | NCL 9.21.16 | ||||||||||
| View Attachment | |||||||||||
| 09/20/2016 | Site Inspection Activity Closed | Hodges, Zachary L. | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 09/19/2016 | ||||||||||
| Activity Closed Date: | 09/21/2016 | Activity Closed By: | HODGES_ZL_1 | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 09/21/2016 | ||||||||
| Comment: | Finished | ||||||||||
| 03/27/2015 | Site Inspection Activity Closed | Hodges, Zachary L. | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 03/27/2015 | ||||||||||
| Activity Closed Date: | 03/27/2015 | Activity Closed By: | HODGES_ZL_1 | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 03/27/2015 | ||||||||
| Comment: | Finished | ||||||||||
| 03/27/2015 | Editable Letter Activity | Hodges, Zachary L. | |||||||||
| Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 02/22/2016 | ||||||||
| Comment: | Finished | ||||||||||
| Attachments: | |||||||||||
| Attachment Date: | 02/22/2016 | User: | HODGES_ZL_1 | ||||||||
| Description: | NCL 3.27.15 | ||||||||||
| View Attachment | |||||||||||
| 12/23/2010 | Site Inspection Activity Closed | Krazit, Jason L. | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 12/23/2010 | ||||||||||
| Activity Closed Date: | 12/23/2010 | Activity Closed By: | KRAZIT_JL_1 | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 12/23/2010 | ||||||||
| Comment: | Finished | ||||||||||
| 12/23/2010 | Emergency Preparedness Information Activity | Krazit, Jason L. | |||||||||
| Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
| Activity Closed Date: | 12/23/2010 | ||||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 12/23/2010 | ||||||||
| Comment: | Finished | ||||||||||
| 12/23/2010 | Editable Letter Activity | Krazit, Jason L. | |||||||||
| Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 12/23/2010 | ||||||||
| Comment: | Finished | ||||||||||
| Events: | |||||||||||
| Event Type: | Document has been sent | Date: | 12/23/2010 | ||||||||
| Comment: | Sent on Thu Dec 23 00:00:00 EST 2010 | ||||||||||
| Attachments: | |||||||||||
| Attachment Date: | 12/23/2010 | User: | KRAZIT_JL_1 | ||||||||
| Description: | NCL | ||||||||||
| View Attachment | |||||||||||
| 01/29/2010 | Violation Open | Krazit, Jason L. | |||||||||
| Significance: | SNC-B | Status: | Open | ||||||||
| Criteria ID: | 1132 | ||||||||||
| Rule: | 62-761.800(2)(b) | ||||||||||
| Comments: | Unmaintained systems are defined in Rule definition #71 as: "a storage tank system that was not closed in accordance with Department rules"; or, "an out-of-service tank system that was not returned to service within the 2, 5 or 10 year period." Note that a system can be out-of-service for 1, 2, 5 or 10 years before becoming unmaintained, and should be in compliance if out-of-service requirements are met. Unmaintained systems are not in violation until after being unmaintained for more than 90 days without closure or being returned to service. This item also covers tank systems found on a piece of property that were not previously registered. Document all time frames discussed with the facility owner/operator. See Rule definition #13 "Discovery" | ||||||||||
| 01/29/2010 | Editable Letter Activity | Krazit, Jason L. | |||||||||
| Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 01/29/2010 | ||||||||
| Comment: | Finished | ||||||||||
| Attachments: | |||||||||||
| Attachment Date: | 01/29/2010 | User: | KRAZIT_JL_1 | ||||||||
| Description: | NCL | ||||||||||
| View Attachment | |||||||||||
| 01/29/2010 | Site Inspection Activity Closed | Krazit, Jason L. | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 01/29/2010 | ||||||||||
| Activity Closed Date: | 01/29/2010 | Activity Closed By: | KRAZIT_JL_1 | ||||||||
| Events: | |||||||||||
| Event Type: | Activity has been finished | Date: | 01/29/2010 | ||||||||
| Comment: | Finished | ||||||||||
| 09/23/2008 | Site Inspection Activity Closed | Henderson, Sylvia A. | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 09/23/2008 | ||||||||||
| Activity Closed Date: | 09/23/2008 | Activity Closed By: | HENDERSON_SA_1 | ||||||||
| Comments: | |||||||||||
| Comment Date: | 08/04/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | RD: Visual Sump & dispensers SIRS, cathodic protection, acrificial anode cp, MECHANICAL LINE LEAK DETECTIOPN | ||||||||||
| 09/23/2008 | Editable Letter Activity | Henderson, Sylvia A. | |||||||||
| Activity Title: | County Subsequent Non-Compliance Letter | Activity Status: | Closed | ||||||||
| Comments: | |||||||||||
| Comment Date: | 10/23/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | Lining - APT Dispenser Liners- Environ | ||||||||||
| 06/04/2008 | Attachment | Henderson, Sylvia A. | |||||||||
| 06/04/2008 | Editable Letter Activity | Henderson, Sylvia A. | |||||||||
| Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
| Comments: | |||||||||||
| Comment Date: | 08/04/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | 1. Must remove strom water and product as not to contaminate the soil or groundwater 2. Must provide financial responsibility/insurance 3. Must provide visuals monitoring - recordkeeping 4. Must provide this information within 5 days to this office fax to 850 875-9215 5 A reinspection will be conducted. | ||||||||||
| 06/04/2008 | Site Inspection Activity Closed | Henderson, Sylvia A. | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 06/04/2008 | ||||||||||
| Activity Closed Date: | 06/04/2008 | Activity Closed By: | HENDERSON_SA_1 | ||||||||
| Comments: | |||||||||||
| Comment Date: | 06/26/2007 | User: | KRAZIT_JL_1 | ||||||||
| Description: | Release detection is monthly visuals. Piping above ground. Recommend removing leaves from secondary containment. | ||||||||||
| 06/04/2008 | Violation Open | Henderson, Sylvia A. | |||||||||
| Significance: | Minor | Status: | Open | ||||||||
| Criteria ID: | 2159 | ||||||||||
| Rule: | 62-762.821(2)(b)4. | ||||||||||
| Comments: | Facility must provide documentation (invoices, work orders) that the system defect has been repaired. These invoices will typically describe the problem, and how the repair was made. If it can not or will not be repaired, was the system closed? | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 08/04/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | 60 psi 12,000 dual compartmentd gass, 4,00 Gall diesel AST Hydro Passed no leaks | ||||||||||
| 06/04/2008 | Violation Open | Henderson, Sylvia A. | |||||||||
| Significance: | SNC-B | Status: | Open | ||||||||
| Criteria ID: | 2089 | ||||||||||
| Rule: | 62-762.611(2)(b) | ||||||||||
| Comments: | Mark this as out of compliance if the facility is not performing visual inspections or is not recording the results monthly. Walk around and look at the tank, containment, all system components, valve and hydrant pits if applicable, and piping. Record your observations. Review monthly records. Does the physical evidence support the facility written record? Look for evidence of wetting, discoloration, blistering, corrosion, cracks, structural damage, and leakage. Examine the tank, saddle, containment inner and outer walls, containment floors, dike height. Note that this applies to all visible parts of an AST system. This rule and 762.611(2)(a)2 deals with release detection for Category-A and B ASTs only. Rule 762.611(1)(b) covers release detection for Category-C systems. Rules 762.611(3)(a)1, 762.611(3)(a)2, 762.611(3)(b), 762.611(3)(c), 762.611(3)(d)1 and 762.611(3)(d)2 deal with all piping release detection. | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 08/04/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | Installing 4,000; 12,000 gallon AST. | ||||||||||
| 06/04/2008 | Violation Open | Henderson, Sylvia A. | |||||||||
| Significance: | Minor | Status: | Open | ||||||||
| Criteria ID: | 1124 | ||||||||||
| Rule: | 62-761.710(3)(a), 62-761.710(3)(b), 62-761.710(3)(c), 62-761.710(3)(d), 62-761.710(3)(e), 62-761.710(3)(f), 62-761.710(3)(g), 62-761.710(3)(h) | ||||||||||
| Comments: | The Rule cites does not list routine operation and maintenance records. If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. Periodic inspections and tank system measurements - rules 62-761.610(3)(a)1, 62-761.700(4)-(5) & 62-761.700(6) b. Supporting claims for equipment in use at facility. - rule 62-761.600(1)(a)3 c. History of what has been done at facility - see 62-761.500 rules. d. Cathodic protection system history - rules 62-761.500(1)(e)1 & 62-761500(1)(e)3 e. Site suitability determination - this document must be updated when site conditions change- rule 62-761.600(1)(f) f. Vapor monitoring plan - this document must be updated annually - rule 62-761.600(1)(g) g. Closure reports - rule 62-761.800(3)(d) h. Single check valve - PSSC documentation that no other buried valves exist - rule 62-761.610(3)(a)1 | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 08/01/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | Less Than 1/2" of product and or water in fill port | ||||||||||
| 06/04/2008 | Violation Open | Henderson, Sylvia A. | |||||||||
| Significance: | Minor | Status: | Open | ||||||||
| Criteria ID: | 1122 | ||||||||||
| Rule: | 62-761.710(1) | ||||||||||
| Comments: | Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period. | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 07/31/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | See Annual Compliance Letter for attachments | ||||||||||
| 06/04/2008 | Violation Closed | Henderson, Sylvia A. | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Criteria ID: | 1002 | ||||||||||
| Rule: | 62-761.400(2)(a) | ||||||||||
| Comments: | Does STCM accurately reflect the tanks at the facility? This question concerns the registration process and payment of fees only - it is not about accurate registration. Check the number of tanks listed on the registration placard. Can the facility owner/operator produce a registration form to document submittal to DEP? Does STCM show that all DEP fees are paid? At the time of tank closure, a registration form should be submitted showing the change in tank codes. | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 07/31/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | Release detection not performed at least once a month. Please provide for the period covering 11/08/2007 | ||||||||||
| 06/04/2008 | Violation Closed | Henderson, Sylvia A. | |||||||||
| Significance: | SNC-B | Status: | Closed | ||||||||
| Criteria ID: | 1004 | ||||||||||
| Rule: | 62-761.400(3)(a)1. | ||||||||||
| Comments: | There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2). | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 07/31/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | Recommend: Removal of all foliage/grass and objects adjacent tanks. Please allow a clear view of the secondary containment wall to ensure observation for leaks and containment wall breaches. | ||||||||||
| 06/04/2008 | Violation Open | Henderson, Sylvia A. | |||||||||
| Significance: | Minor | Status: | Open | ||||||||
| Criteria ID: | 1123 | ||||||||||
| Rule: | 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h) | ||||||||||
| Comments: | If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3) | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 08/01/2008 | User: | HENDERSON_SA_1 | ||||||||
| Description: | Southside One Stop has had Major out of compliance, non-compliance leters issued for 20080731 and 20071108. Please review out of compliance photos for numerous violations. | ||||||||||
| 06/04/2008 | Attachment | Henderson, Sylvia A. | |||||||||
| 12/26/2007 | Issue Document Activity | Gillman, Mark | |||||||||
| Activity Status: | Closed | ||||||||||
| Contact Name: | Denise Franklin | Activity Closed Date: | 12/26/2007 | ||||||||
| 07/02/2007 | Enforcement Tracking Activity | Gillman, Mark | |||||||||
| Activity Status: | Open | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 07/27/2007 | User: | GILLMAN_M | ||||||||
| Description: | Accepted. | ||||||||||
| 12/22/2006 | Enforcement Referral Activity - OLD Activity | Krazit, Jason L. | |||||||||
| No data found! | |||||||||||
| 12/21/2006 | Enforcement Referral Activity | Krazit, Jason L. | |||||||||
| Activity Result: | Accepted | Activity Status: | Closed | ||||||||
| Activity Closed Date: | 07/02/2007 | ||||||||||
| Events: | |||||||||||
| Event Type: | Activity/Document was accepted on this date | Date: | 07/02/2007 | ||||||||
| Comment: | Possible Indigent Consent Order Case. The District is waiting for financial analysis from Tallahassee. | ||||||||||
| Events: | |||||||||||
| Event Type: | Activity/Document was acknowledged on this date | Date: | 07/02/2007 | ||||||||
| Comment: | Recieved and aknowledged. | ||||||||||
| Events: | |||||||||||
| Event Type: | Activity has been submitted for approval | Date: | 12/22/2006 | ||||||||
| Comment: | Franklins Bait and Tackle is not doing business and is for sale. Mrs. Franklin said she cant afford insurance or tank removal. She doesnt have her placard,records, test, insurance. She did have the tanks pumped and each one has less than 1" of product. | ||||||||||
| 12/20/2006 | Violation Open | Krazit, Jason L. | |||||||||
| Significance: | SNC-B | Status: | Open | ||||||||
| Criteria ID: | 1004 | ||||||||||
| Rule: | 62-761.400(3)(a)1. | ||||||||||
| Comments: | There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2). | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 06/25/2007 | User: | KRAZIT_JL_1 | ||||||||
| Description: | Store closed at time of inspection for upgrade. | ||||||||||
| 12/20/2006 | Editable Letter Activity | Krazit, Jason L. | |||||||||
| Activity Title: | District Non-Compliance Letter | Activity Status: | Closed | ||||||||
| Events: | |||||||||||
| Event Type: | Document has been sent | Date: | 12/20/2006 | ||||||||
| Comment: | Sent on Wed Dec 20 00:00:00 EST 2006 | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 06/27/2007 | User: | KRAZIT_JL_1 | ||||||||
| Description: | Release detection is visuals of tank and dispensers. All piping is above ground. | ||||||||||
| Attachments: | |||||||||||
| Attachment Date: | 12/20/2006 | User: | KRAZIT_JL_1 | ||||||||
| Description: | NCL Report | ||||||||||
| View Attachment | |||||||||||
| 12/20/2006 | Violation Open | Krazit, Jason L. | |||||||||
| Significance: | Minor | Status: | Open | ||||||||
| Criteria ID: | 1128 | ||||||||||
| Rule: | 62-761.800(1)(c) | ||||||||||
| Comments: | Know the start date of the out-of-service period, and document it. Keep track of the time period and advise the facility owner/operator of approaching deadline. Note: Rule definition #40 includes in the definition of "out-of-service - ten years for storage tank systems with secondary containment". | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 06/25/2007 | User: | KRAZIT_JL_1 | ||||||||
| Description: | Release detection is veeder root TLS-350, monthly visuals and LLD. Piping is double wall. | ||||||||||
| 12/20/2006 | Violation Open | Krazit, Jason L. | |||||||||
| Significance: | Minor | Status: | Open | ||||||||
| Criteria ID: | 1003 | ||||||||||
| Rule: | 62-761.400(2)(f) | ||||||||||
| Comments: | All federal facilities with USTs will have a placard. Per FS 376.3077, "It is unlawful for any owner, operator, or supplier to pump or otherwise deposit any motor fuel into a tank required to be registered under section 376.303 FS, unless proof of valid registration is displayed on such tank itself or the dispensing or measuring device connected thereto or, where appropriate, in the office or kiosk of the facility where the tank is located." Penalties can be assessed to the facility owner for failure to properly register tank systems. Note that penalties can be assessed to the supplier that delivers motor fuel to an unregistered facility. Check the details on the placard. Do they agree with the location you are inspecting? Owners of multiple facilities may switch placards by mistake. Placards are not always issued or received in a timely manner at the change of year period (June and July). Provide the DEP Tallahassee phone number to the facility so they may resolve problems (850) 245-8850; (850) 245-8840. Check STCM in the registration/placard section for the date that the payment was made and the date that the placard was issued. The location of the placard in plain view can be subjective in interpretation: a. For vehicular fuel facilities, plain view is meant to allow the transport delivery driver to view the placard prior to delivering fuel. b. A legal definition is an exception to the general requirement of a valid search warrant to legitimize a search or seizure; a search implies prying into hidden places, and it is not a search to observe what is open to view. | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 06/25/2007 | User: | KRAZIT_JL_1 | ||||||||
| Description: | Abandoned tanks. Cannot reach owners. Less than 1" of product in both UST's. | ||||||||||
| 12/20/2006 | Violation Open | Krazit, Jason L. | |||||||||
| Significance: | Minor | Status: | Open | ||||||||
| Criteria ID: | 1002 | ||||||||||
| Rule: | 62-761.400(2)(a) | ||||||||||
| Comments: | Does STCM accurately reflect the tanks at the facility? This question concerns the registration process and payment of fees only - it is not about accurate registration. Check the number of tanks listed on the registration placard. Can the facility owner/operator produce a registration form to document submittal to DEP? Does STCM show that all DEP fees are paid? At the time of tank closure, a registration form should be submitted showing the change in tank codes. | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 06/25/2007 | User: | KRAZIT_JL_1 | ||||||||
| Description: | Release detection is monthly visuals, ATG-Gilbarco EMC, Line leak detector. Piping is DW fiberglass. Godfrey Dickson performed inspection but never closed. | ||||||||||
| 12/19/2006 | Site Inspection Activity Closed | Krazit, Jason L. | |||||||||
| Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
| On-Site Start Date: | 12/19/2006 | ||||||||||
| Activity Closed Date: | 12/20/2006 | Activity Closed By: | KRAZIT_JL_1 | ||||||||
| Comments: | |||||||||||
| Comment Date: | 06/24/2007 | User: | KRAZIT_JL_1 | ||||||||
| Description: | Release dection is Gilbarco ATG,Visuals and line leak detecter. Piping for underground is fiberglass, above ground is galvanized. | ||||||||||
| 10/31/2005 | Violation Open | Unknown, User | |||||||||
| Significance: | Minor | Status: | Open | ||||||||
| Criteria ID: | 1125 | ||||||||||
| Rule: | 62-761.800(2)(a)1.a., 62-761.800(2)(a)1.b., 62-761.800(2)(a)1.c., 62-761.800(2)(a)1.d., 62-761.800(2)(a)3. | ||||||||||
| Comments: | Per Rule definition #40, "Out-of-service" means a storage tank system that: (a) Is designated as an out-of-service system by owner or operator notification to the Department on Form 62-761.900(2), F.A.C.; (b) Is empty as defined in Rule 62-761.200(18), F.A.C. "Empty" means all regulated substances have been removed so that no more than one inch in depth or 0.3 percent by weight of total system capacity of regulated substances remains in the storage tank system.; and (c) Does not have regulated substances transferred into or withdrawn from the tank as specified in subsection 62-761.800(1), F.A.C., for a maximum time of: 1. Two years of being taken out-of-service for USTs; or 2. Ten years of being taken out-of-service for storage tank systems with secondary containment. If all of the above are not met, then consider the system as still in service status for enforcement purposes. Record discrepancies accordingly. Document the reason for placement in this status. Monitor the time limitations. Verify that the tank has been emptied. Have the tank stuck or check the gauging device. Systems with secondary containment need not perform monthly release detection. | ||||||||||
| 10/31/2005 | Legacy Activity | Brooks, Addie | |||||||||
| Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
| 03/08/2005 | Violation Closed | Brooks, Addie | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 761.820(1)(a),(b),(c) | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 08/17/2020 | User: | BECKER_GT_1 | ||||||||
| Description: | OCEPD received testing documents for the new AST: Fill port hydro test; AST interstitial integrity test; Krueger interstitial leak gauge; Clock fuel level gauge. | ||||||||||
| 03/08/2005 | Legacy Activity | Brooks, Addie | |||||||||
| Activity Name: | NON-COMPLIANCE LETTER ISSUED | Activity Status: | Closed | ||||||||
| 03/08/2005 | Legacy Activity | Brooks, Addie | |||||||||
| Activity Name: | TANK COMPLIANCE RE-INSPECTION | Activity Status: | Closed | ||||||||
| 10/26/2004 | Violation Closed | Brooks, Addie | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 761.700(1)(c)3 | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 01/21/2020 | User: | DASHTAKI_K_1 | ||||||||
| Description: | See attached Liquid status print out from TLS-350. All Functions Normal. | ||||||||||
| 10/26/2004 | Legacy Activity | Brooks, Addie | |||||||||
| Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
| 10/26/2004 | Violation Closed | Brooks, Addie | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 761.640(1)(c) | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 01/21/2020 | User: | HATCHER_JD_1 | ||||||||
| Description: | VISUAL INSPECTION: 1/21/2020 Placard: ok FR: ok CFR: ok Tank: ok Piping: ok Dispenser: Top mounted. Overfill: site gauge. Monthly Visuals: provided and current. Leak detection: Monthly visuals with manual interstice checks. | ||||||||||
| 10/26/2004 | Violation Closed | Brooks, Addie | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 761.600(5) | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 01/21/2020 | User: | SUAREZ_J | ||||||||
| Description: | A Petroleum Storage Tank Inspection was conducted on December 18, 2019, by Juliana Suarez-Mitnik and David Maloney, Environmental Specialists with the Florida Department of Environmental Protection (Department) and Carl Joseph, Building Manager with Broward County Facilities Management. The facility had one 6,000-gallon underground tank with double-wall piping connected to an emergency generator. The tank has a suction system. The piping sump was dry with some signs of rust, the boots were pulled back. The spill bucket is double wall, dry and no signs of rust. The tank is monitored by a Veeder-Root TLS 300C that monitors the interstice, and it has a sensor for overfill; however, there is no audible or visual alarm near the tank to let anyone know if the tank is filled to 95% capacity . The facility has a contract with Florida Metro to do the monthly inspections where they check the Veeder-Root sensors and visually inspect the piping sump and the spill bucket. All Paperwork has not been provided to the Department. The facility did not provide the Department with the annual operability test for the Veeder- Root; the facility has not designated a specific overfill protection. the facility did not provide the Department with the integrity test for the piping sump and the spill bucket. The Facility has a designated person as an operator A and B, however, the facility has not provided the name of the C certified operator to the Department. The Department recommends cleaning, sealing ad painting any components beginning to show signs of rust, corrosion. Facility Contact information Carl Joseph, Building Manager Public Works Department, Facilities Management Division Office: (954) 357-6480 Cell: (954) 214-4880 CARLJOSEPH@broward.org The inspection report will be emailed to Freddy Ulloa, along with the Compliance Assistance Letter. | ||||||||||
| 10/09/2003 | Violation Closed | Brock, Melissa | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 700(1)(b)2a | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 02/28/2018 | User: | JARRETT_SE_1 | ||||||||
| Description: | Dispenser #3 checked for leakage on the left side. Possible minor seepage still occurring but could not verify at the time of the inspection; recommend closely monitoring during the monthly release detection inspections. | ||||||||||
| 10/09/2003 | Legacy Activity | Brock, Melissa | |||||||||
| Activity Name: | NON-COMPLIANCE LETTER ISSUED | Activity Status: | Closed | ||||||||
| 10/09/2003 | Legacy Activity | Brock, Melissa | |||||||||
| Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
| 10/09/2003 | Violation Closed | Brock, Melissa | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 600(2)(d) | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 02/28/2018 | User: | PAYNE_CL_1 | ||||||||
| Description: | Received DRF stating that closure assessment during spill bucket replacement activities included the collection of one laboratory soil sample at each spill bucket area. Laboratory analytical data for the RUL spill bucket soil sample indicated a Chapter 62-777, FAC Table II exceedance. | ||||||||||
| 10/01/2002 | Legacy Activity | Brock, Melissa | |||||||||
| Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
| 11/06/2001 | Legacy Activity | Brock, Melissa | |||||||||
| Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
| 11/30/2000 | Legacy Activity | Brock, Melissa | |||||||||
| Activity Name: | NON-COMPLIANCE LETTER ISSUED | Activity Status: | Closed | ||||||||
| 11/28/2000 | Violation Closed | Brock, Melissa | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 640(2)(c)4 | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 04/26/2012 | User: | CRAFT_TT_1 | ||||||||
| Description: | 2012.04.23 - Received BOI test results (passed). | ||||||||||
| 11/28/2000 | Legacy Activity | Brock, Melissa | |||||||||
| Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
| 11/28/2000 | Violation Closed | Brock, Melissa | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 640(1)(c) | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 04/26/2012 | User: | OWENS_JS_1 | ||||||||
| Description: | Tanks installed in 1988 - no BOI required - recommended BUT not required. | ||||||||||
| 11/28/2000 | Violation Closed | Brock, Melissa | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 700(1)(c)1 | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 04/26/2012 | User: | OWENS_JS_1 | ||||||||
| Description: | Breach of Integrity test due next January 2013 - every 5 years - last tested 1/2008. | ||||||||||
| 05/15/2000 | Legacy Activity | Unknown, User | |||||||||
| Activity Name: | TANK INSTALLATION - FINAL INSPECTION | Activity Status: | Closed | ||||||||
| 11/30/1999 | Violation Closed | Unknown, User | |||||||||
| Significance: | SNC-A | Status: | Closed | ||||||||
| Rule: | 510(2)(d) | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 11/30/2010 | User: | COOK_JH_1 | ||||||||
| Description: | Single-walled steel UST -- Modern Welding model AB-50, compartmented 4000/2000. Single-walled steel integral piping. Sacrificial anode CP. Removed with all components August 2010. | ||||||||||
| 11/30/1999 | Legacy Activity | Unknown, User | |||||||||
| Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
| 11/30/1999 | Violation Closed | Unknown, User | |||||||||
| Significance: | SNC-B | Status: | Closed | ||||||||
| Rule: | 610(4)(a)1 | ||||||||||
| 11/30/1999 | Violation Closed | Unknown, User | |||||||||
| Significance: | Minor | Status: | Closed | ||||||||
| Rule: | 700(1)(b)1 | ||||||||||
| Comments: | |||||||||||
| Comment Date: | 11/30/2010 | User: | WINN_JP_1 | ||||||||
| Description: | Containment has been sealed, although apparently with a material not included on the approved equipment list. Violation remains open. | ||||||||||
| 09/30/1998 | Legacy Activity | Unknown, User | |||||||||
| Activity Name: | UST ROUTINE COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||