Report Run Date: 04/25/2021        Last Data Refresh: 04/24/2021        Report Generated from DOPPLER
 
Facility ID: 8518678
Facility Name: PANAMA CITY CITY-MASSALINA
 
02/24/2020 Electronic Communication Activity Throckmorton, Jenna
Activity Closed Date: 02/24/2020 Activity Status: Closed
Date: 02/24/2020
Recipient: Jacky Pruitt
Sender: Jenna Throckmorton
Subject: Notice of 1st Contact
Message: See Attached
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
Attachments:
Attachment Date: 02/24/2020 User: THROCKMORTON_JN
Description: Notice of 1st Contact
View Attachment
05/22/2019 Enforcement Tracking Activity Gillman, Mark
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 06/19/2020
Events:
Event Type: Activity has been finished Date: 06/19/2020
Comment: Finished
Attachments:
Attachment Date: 04/27/2020 User: THROCKMORTON_JN
Description: Warning Letter
View Attachment
05/20/2019 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 05/22/2019
Events:
Event Type: Activity has been submitted for approval Date: 05/20/2019
Comment: Submitted for approval by: Muhammad Rafique Khan: 5/16/2019 email was sent for violation response, as of today violations are still open.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 05/22/2019
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been assigned Date: 05/22/2019
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 05/22/2019
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 05/22/2019
Comment: Accepted by Mark Gillman: Accepted
05/01/2019 Comment Khan, Muhammad Rafique
Description: called talk to dean,jackie is not in,asked dean to leave him note about test violation response.
02/20/2019 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: jpruitt@pcgov.org Activity Closed Date: 02/20/2019
Events:
Event Type: Activity has been finished Date: 02/20/2019
Comment: Finished
02/19/2019 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/20/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 02/20/2019
Comment: Finished
Attachments:
Attachment Date: 02/20/2019 User: WILSON_ML_1
Description: Compliance Assistance Offer Letter
View Attachment
02/12/2019 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 4057
Rule: 62-761.500(7)(e)
02/12/2019 Phone Conversation Activity Khan, Muhammad Rafique
Call Type: Outgoing Activity Status: Closed
Phone Number: (850) 872-3182 Activity Closed Date: 02/19/2019
Subject: called Jackie Pruitt for tci on 2/12/2019 called Jackie for tci on 2-12-2019 ¿ Activity Annual Compliance ¿ » Inspection Activities- Inspection Information - Site Visits - Checklists - AOCs/Violations - Regulatory Data - Comments - Attachments - Participants - Meeting Activities - Electronic Communication Activities - Phone Activities - Activity Actions PANAMA CITY CITY-MASSALINA >> Annual Compliance >> Inspection Activity ¿ Activity Annual Compliance ¿ » Inspection Activities- Inspection Information - Site Visits - Checklists - AOCs/Violations - Regulatory Data - Comments - Attachments - Participants - Meeting Activities - Electronic Communication Activities - Phone Activities - Activity Actions 02/05/2019
Events:
Event Type: Activity has been finished Date: 02/19/2019
Comment: Finished
02/12/2019 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/12/2019
Activity Closed Date: 02/19/2019 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 02/19/2019
Comment: Finished
10/25/2018 Site Inspection Activity Closed Wilson, Monica L
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/18/2018
Activity Closed Date: 10/25/2018 Activity Closed By: WILSON_ML_1
Events:
Event Type: Activity has been finished Date: 10/25/2018
Comment: Finished
Attachments:
Attachment Date: 10/25/2018 User: WILSON_ML_1
Description: 8518678 - Michael
View Attachment
08/08/2016 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: Benjamin Logue, B.S Activity Closed Date: 08/08/2016
Events:
Event Type: Activity has been finished Date: 08/08/2016
Comment: Finished
07/19/2016 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1103
Rule: 62-761.640(4)(a)1., 62-761.640(4)(a)2., 62-761.640(4)(a)3., 62-761.640(4)(a)4.
Comments: Installation - verify that the line leak detector has been installed during the final installation inspection. Compliance - check to see that the unit is present. Examine the annual function test data - a pass alone is not sufficient. The tester must demonstrate 3.0 gph discharge detection for the mechanical (flow restrictor). Note that the electronic (auto shut off) line leak detector does not need an annual test, but must still be able to detect a 0.2 gph leak after it has been tripped at 150% line operating pressure. Replacements - unit must be tested out of the box - function must be proven. 3.0 gph = 185.4 ml/min (To convert milliliters/minute to gallons/hour, multiple the milliliters by 0.0162162; or, 1 gph equals 61.8 ml/min). Values greater than 186 ml/min fail. Values less than 185 ml/min mean that the line leak detector will activate at a more restrictive rate.
07/19/2016 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: 8507536_INF for failed components_10-22-2018
Events:
Event Type: Document has been sent Date: 07/20/2016
Comment: Sent
Events:
Event Type: Activity has been finished Date: 07/20/2016
Comment: Finished
Attachments:
Attachment Date: 07/20/2016 User: WILSON_ML_1
Description: 1st Non-Compliance Letter
View Attachment
07/19/2016 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 07/19/2016
Activity Closed Date: 07/19/2016 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 07/19/2016
Comment: Finished
07/14/2014 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/14/2014
Activity Closed Date: 07/14/2014 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 07/14/2014
Comment: Finished
11/14/2012 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/14/2012
Activity Closed Date: 11/14/2012 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 11/14/2012
Comment: Finished
01/23/2012 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/23/2012
Activity Closed Date: 01/23/2012 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 01/23/2012
Comment: Finished
02/11/2011 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/11/2011
Activity Closed Date: 02/11/2011 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 02/11/2011
Comment: Finished
02/02/2011 Editable Letter Activity Purdy, Elena M.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/02/2011
Comment: Sent on Wed Feb 02 00:00:00 EST 2011
Events:
Event Type: Activity has been finished Date: 02/02/2011
Comment: Finished
Attachments:
Attachment Date: 02/02/2011 User: PURDY_EM_1
Description: Non-Compliance Letter
View Attachment
02/01/2011 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
02/01/2011 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/01/2011
Activity Closed Date: 02/02/2011 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 02/02/2011
Comment: Finished
12/10/2009 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/10/2009
Activity Closed Date: 12/10/2009 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 12/10/2009
Comment: Finished
11/10/2008 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/10/2008
Activity Closed Date: 11/12/2008 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 01/31/2008 User: KHAN_MR_1
Description: TCI =1-31-08 WITH RICK MARTIN. FACILTY HAS 4 TANKS. THREE ARE SUBGENERATOR TANKS,3500,900,850 ALLONS.FOURTH IS 3000 GALLON AST. RELEASE DETECTION=FROM VISUAL INTERSTITIAL OF AST-ELECTRONIC ALARM FOR SUBGENERATOR TANKS.(All of the three gensets with sub-base tanks have electronic monitoring of the rupture) basin for leaks from the primary tank OVERFILL PROTECTION= CLOCK GAUGE/MANUAL GAUGING. ---------------------------------------------------------------------- 850 GALLON =SUBGEN TANK=CLOCK TYPE OVERFILL GAUGE AND DISPLAY PANEL FOR ALARM,SPILL BOX PRESENT.I/S ALARM WORKS. ------------------------------------------------------- 900 GALLON=SUBGEN TANK=CLOCK TYPE OVERFILL GAUGE AND DISPLAY PANEL FOR ALARM,SPILL BOX PRESENT.I/S ALARM WORKS.PER RICK, COULD NOT GO NEAR THE GENERATOR,IT WAS RUNNING WITH LOUD THUNDROUS NOISE.. ---------------------------------------------------------------- 3000 GALLONS-AST WITH CLOCK TYPE GAUGE,2 EMERGENCY AND ONE STACK TYPE VENT, SPILL BUCKET PRESENT, I/S SPACE WAS CHECKED MANUALLY ERIC,WAS DRY. ----------------------------------------- 5300 GALLON IS ASUB GEN TANK,IT IS HUGE,HAVE ASPILL BUCKER 2 EMERGENCY VENTS,ONE STACK VENT,ELECTRONIC AUDIBLE ALARM FOR I/S,WHICH DID NOT WORK.OVERFILL PROTECTON IS MANUALLY GAUGING PER RICK. ------------------------ RDRL AND CERTIFICATION FORMS WERE FILLED AT THE SPOT.
10/23/2007 Comment Khan, Muhammad Rafique
Description: tci-11-23-07 with richard. 83 degrees. Facility is located on massilina and 7th street,(city maintainannce yard. They have one DW ,compartmented tank.INSTALLED IN 1982, COMPARTMENTED. Release detection is i/s monitoring MANUALLY THROUGH PORT. Overfill protection = ball checks. They have auto stick junior atg, but used only for inventory purpose. Rdrl= posted in staf assistant's office. Ins, cofr = ok. Tank test = not required ,dw tank. Illd test = annual, last done =12-6-05, due =tomorrow 0n 12-6-06. Piping = double walled. Environ Eq # 511.No annual test required. Dispenser liner = Environ Eq #439 Cathodic protection = n/r. Sensors = none. STP= 2, deep green Environ Eq # = 540, had very little water at the bottom(condensation). year BEFORE LAST spill bucket failed hydrotest, were replaced, both had little product in them = ok. Tank i/s is checked by Richard monthly and currently it is dry(only one i/s ). JAMIE WORK IN THE OFFICE. ----------------------- NOTE REGULAR STP WAS FULL OF WATER DUE TO LAST WEEKS RAIN, BUT WATER WAS TAKEN OUT IN MY PRESENCE. THANKS TO RICH FOR HELP AND KEEPING FACILITY AND PAPERWORK IN EXCELLENT SHAPE.
10/23/2007 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/23/2007
Activity Closed Date: 10/23/2007 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 11/22/2006 User: KHAN_MR_1
Description: 12,000 GL. DW, Steel, Two (2) compartment (6/6). Alabama tank F-921 Piping - DW/ APT -suction EQ #569 Overfill protection-Clock gauge w/overfill alarm OPW EQ610 Release detection-I/S space & monthly visual check of transition sump and dispenser liners.
10/23/2007 Attachment Khan, Muhammad Rafique
10/23/2007 Attachment Khan, Muhammad Rafique
09/28/2007 Enforcement Referral Activity Bristol, Susan M.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 09/28/2007
Events:
Event Type: Activity/Document was accepted on this date Date: 09/28/2007
Comment: The Northwest District Storage Tank Section accepts the enforcement referral from the Northwest District Storage Tank Section.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 09/28/2007
Comment: The Northwest District Storage Tank Section acknowledges the enforcement referral.
Events:
Event Type: Activity has been submitted for approval Date: 09/28/2007
Comment: The Northwest District Storage Tank Section is submitting this enforcement referral to the Northwest District Storage Tank Section.
Comments:
Comment Date: 12/06/2007 User: BRISTOL_S
Description: The Northwest District Storage Tank Section acknowledges the submittal of the enforcement referral activity to the Northwest District Storage Tank Section for the overdue SAR for the December 15, 2006 discovery of a discharge.
09/28/2007 Enforcement Tracking Activity Bristol, Susan M.
Activity Status: Open
Comments:
Comment Date: 12/06/2007 User: BRISTOL_S
Description: The Northwest District Storage Tank Section accepts the enforcement referral for the overdue SAR for the December 15, 2006 discovery of a discharge.
12/05/2006 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/05/2006
Activity Closed Date: 12/05/2006 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 11/21/2006 User: KHAN_MR_1
Description: Dana suttle trucking. Facility is located on transmitter ave. Tank = Alabama fire guard EQ# .12000 gallon D/W ast. Was installed on i/2001. INS = OK COFR = OK RDRL = OK VISUAL = OK. Release detection = visual monitoring of tank i/s (pop up gauge )and dispenser liners. Overfill protection = fuel gauge, clock type. Tank exterior, spill bucket, piping, dispenser liners, hoses lookedok. Alarm = audible = ok. They have a veeder root TLS300c EQ = 196.for only inventory purposes. DAVID SMITH IS OFF TODAY SO JUSTIN WOULD BE THE INSPECTION PERSON AT FACILITY.
06/21/2006 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: NOTE TO FILE Activity Closed Date: 06/22/2006
Comments:
Comment Date: 11/30/2006 User: KHAN_MR_1
Description: Facility have TOTAL FIVE, OF WHICH 4 ARE dw OWEN CORNING tanks (WERE USED TANKS PRIOR TO INSTALLTION) EQ # 191. PIPING = AMERON EQ # 291 AND ENVIRON EQ # 378 STP =APT EQ # 423. DISPENSER SUMP = ENVIRON GREEN EQ # 439 RELEASE DETECTION ATG VR 350 EQ # 033.OVERFILL PROTECTION = FLAPPER.
06/20/2006 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 06/20/2006
Activity Closed Date: 06/20/2006 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 11/20/2006 User: KHAN_MR_1
Description: 4000 Gl. AST steel, single walled. Piping -Steel/no contact with soil. Overfill Protection- Concrete secondary containment. Release Detection -Visual Inspection, stick gauge of tanks.
06/20/2006 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 06/20/2006
Activity Closed Date: 06/20/2006 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 11/21/2006 User: KHAN_MR_1
Description: Dana suttle trucking. Facility is located on transmitter ave. Tank = Alabama fire guard EQ# .12000 gallon D/W ast. Was installed on i/2001. INS = OK COFR = OK RDRL = OK VISUAL = OK. Release detection = visual monitoring of tank i/s (pop up gauge )and dispenser liners. Overfill protection = fuel gauge, clock type. Tank exterior, spill bucket, piping, dispenser liners, hoses lookedok. Alarm = audible = ok. They have a veeder root TLS300c EQ = 196.for only inventory purposes. tank is showing some rust bands but ok. DAVID SMITH IS OFF TODAY SO JUSTIN GOTSECHALL WOULD BE THE INSPECTION PERSON AT FACILITY. kristi is the office exective.Bob also here.
12/15/2005 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
12/14/2005 Violation Closed Unknown, User
Significance: Minor Status: Closed
Criteria ID: 1010
Rule: 62-761.450(2)(a)1., 62-761.450(2)(a)2., 62-761.450(2)(a)3., 62-761.450(2)(a)4., 62-761.450(2)(a)5., 62-761.450(2)(a)6., 62-761.450(2)(a)7.
Comments: Multiple incidents occurring at the same time at the facility may be reported on one form. #1-3 - Evidence of these types of INF situations are generally found during the inspector's paperwork review. Ask the facility representative what action they took in response, and in what time frame. If the situations are resolved within 24 hours, the owner/operator is not required to submit an INF to the local program. However, the actions they took to resolve the issue must be documented. #4-5, and 7 - Evidence of these types of situations are generally found during the outside or physical portion of the inspection. Give the facility owner/operator 24 hours to resolve, provided they document their actions. If they can not resolve the issues then they must submit the INF, at which time the two week investigative window opens. #6 - Evidence of this type of situation may be found during the physical examination of the release detection device (e.g. alarm mode), or during the examination of the records associated with the method. Note: Inspectors may find events that qualify as incidents during their review of the facility's paperwork. Such issues must have been resolved within 24 hours if an INF was not submitted at the time of the event.
02/03/2005 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: PIPING: GREEN ENVIRON; DIESEL - WHITE TCI
01/06/2005 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.500(5)(a)
Comments:
Comment Date: 06/16/2020 User: HATCHER_JD_1
Description: Covid concerns. No signature obtained
01/06/2005 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PIPING: GASOLINE-GREEN ENVIRON; DIESEL-WHITE TCI
01/13/2004 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PIPING: GASOLINE-GREEN ENVIRON; DIESEL-WHITE TCI
05/27/2003 Legacy Activity Pinkovsky, Dennis D.
Activity Name: DISCHARGE SUSPECTED - NO RELEASE FOUND Activity Status: Closed
Completion Notes: DSNR FOR DRY TANK INTERSTICE AFTER ATG ALARM (ATG MALFUNCTION).
03/18/2003 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: PIPING: GAS-GREEN ENVIRON DIESEL: WHITE TOTAL CONTAINMENT?
02/13/2003 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
01/23/2003 Legacy Activity Pinkovsky, Dennis D.
Activity Name: INCIDENT REPORT FORM RECEIVED Activity Status: Closed
Completion Notes: INF FOR ATG ALARM.
01/21/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 400(2)(a)6
Comments:
Comment Date: 08/29/2016 User: PAYNE_CL_1
Description: Financial Responsibility is not required for ASTs that are properly taken out of service.
01/21/2003 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/21/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 710(2)
Comments:
Comment Date: 08/29/2016 User: MOLDENHAUER_HL_2
Description: Draft inspection emailed to: Administration@citrapac.com
01/21/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)3
Comments:
Comment Date: 08/29/2016 User: JARRETT_SE_1
Description: Received a copy of the release detection inspection record for the inspection performed on 08/23/2016.
01/21/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(a)1
Comments:
Comment Date: 08/29/2016 User: JARRETT_SE_1
Description: Received a copy of the release detection inspection record for the inspection performed on 08/23/2016.
01/21/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 640(3)(d)
Comments:
Comment Date: 08/29/2016 User: KEIM_MJ_1
Description: Tank Compliance Inspection report sent via e-mail to Lew Petteway, 352-207-1121, lewis.petteway@centurylink.com and Jennifer Scarpino, 407-889-1531, jennifer.scarpino@centurylink.com and Robert Bridge, 352-351-3350, robert.a.bridge@centurylink.com
01/21/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 500(2)(d)1
Comments:
Comment Date: 08/29/2016 User: MOLDENHAUER_HL_2
Description: System was installed by Tom Jackson, Onsite Power Services, (863) 287-0051; tejac@aol.com On-Site Breach of Integrity test conducted on the tank interstitial on 4/29/2016 by Petroleum Compliance Solutions Inc.; Mr. Richard Parsons, RQ66551. 1000 gallon double wall sub base generator tank (Engineering Manufacturing Corp-EQ-700) (UL # A61049237) Morrison Bros 7 gallon Spill containment Fig 518 EQ-345 10 Series Fluid Level Switches, mfg by Advanced Control Technology Inc. EQ-832 Regular and emergency venting on primary tank Emergency venting on secondary tank Rochester inventory gauge
01/21/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 450(2)(a)
Comments:
Comment Date: 08/29/2016 User: PICKERING_M_1
Description: On 08/29/2016 - MP met with Shane Hill of Suncoast Schools FCU for a closure inspection of Tank #1. Tank #1: (1) Custom Tank Technology 1,000 gallon double walled steel emergency generator (EQ# 249) AST containing diesel fuel. Exact removal date according to facility records was on 08/27/2016. Tank was removed by Power Distribution according to closure application. No closure assessment required. A double walled AST with no history of a positive response of the release detection system is not required to conduct a closure assessment. This facility has no record or any discharges. No program eligibility. Operator stated that the tank was in good condition at time of tank removal. No physical issues noted from previous inspections. According to closure application, tank#1 is being relocated to another Suncoast Shools facility located at 5701 E Hillsborough Ave. #2415, Tampa Fl. Operator stated that tank# 1 has been empty for a year. There were no signs of spillage noted during inspection. No signs of contamination (soil staining, sheen, product, petroleum odor) noted. Area where tank was located is now vacant, see photo. Piping was contained in the storage tank/generator unit. Removed with tank. No forms left at the site. STRF was submitted for closure of Tank #1 on 8/24/2016. Monthly inspection records for from April 2015 to July 2015 were reviewed. Records from August 2015 to present were not available for review. Operator stated that the tank has not been used since July 2015. Reminded operator to ensure that all visual inspections are performed once a month not to exceed 35 days in between unless tank has been properly placed out of service with EPC. Tank #1 was removed from site on 8/27/2016. No further action required. Disposal manifest for tank and product must be submitted to EPC within 60 days.
01/21/2003 Violation Closed Godwin, Christine
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 08/29/2016 User: MERRITT_S
Description: Facility Contacts: Alan Hagans, FDOT, alan.hagan@dot.state.fl.us, (850) 330-1511, District Contamination Impacts Coordinator Facility Operator: Anandkumar Shah (Alan Shah), magicmart31@gmail.com, 850-319-8224
02/04/2002 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
01/08/2002 Violation Closed Godwin, Christine
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 09/02/2014 User: BECKER_GT_1
Description: Site visit performed today to discuss with contractors onsite about the relocation of the two 1,000-gal ASTs. The ASTs are being moved to a different location on OIS Executive property but are still owned and operated by OIA. No closure/install is necessary.
01/08/2002 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/08/2002 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 710(2)
Comments:
Comment Date: 09/02/2014 User: MOLDENHAUER_HL_1
Description: Email address Rosalindbar@msn.com
08/27/2001 Legacy Activity Godwin, Christine
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
08/23/2001 Legacy Activity Godwin, Christine
Activity Name: TANK CLOSURE INSPECTION Activity Status: Closed
03/30/2001 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
01/18/2001 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)3
Comments:
Comment Date: 07/24/2012 User: PUCCI_SA_1
Description: Tank: D/W Phoenix Envirovault (Eq#013) Pneumercator TMS 3000 (Eq#303) Krueger Level Gauge Morrison Bros. Co. Anti-Siphon Valves (Model #910er) Underground D/W Ameron 3000l Dualoy (Eq#378) Piping
01/18/2001 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/31/2000 Comment MIGRATION
Description: COMPLIANCE: TK00341/0385-18678
10/31/2000 Comment MIGRATION
Description: COMPLIANCE: TANKS CLEANUP
03/06/2000 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
01/18/2000 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 510(1)(b)3
Comments:
Comment Date: 01/14/2011 User: KHAN_MR_1
Description: AFTER SEVERAL PHONE CALLS,FINALLY WENT TO FACILTY AND PICKED UP THE INSURANCE-, WHICH IS CHARTIS AND VAILD FROM 9-1-2010 TO 9-1-2013.THIS WILL CLEAR THE VIOLATION.62-762.401(3)(a)1.# 2004
01/18/2000 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/18/2000 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 640(3)(d)
Comments:
Comment Date: 01/14/2011 User: SHER_RC_1
Description: On site for a compliance re-inspection as a follow-up to the annual inspection of 12/14/2010. Met with Gary Jefferies of Hi-Lift Marina. FIRST not available---no rep. signiture. The following was observed: ---A 15 day DERM Non-Compliance letter (NCL) was issued for the following previously cited compliance issues: two compliance wells between the tank and the dispensers are inaccessible; the NE corner compliance well has no cover. ---Facility diagram included; facility photo will be attatched as soon as possible.
01/18/2000 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(a)3
Comments:
Comment Date: 01/14/2011 User: SHER_RC_1
Description: On site for a compliance re-inspection. Met with the Station Manager, Lourdes Moncayo. FIRST not available---no rep. signiture. The following was observed: ---A 15 day DERM Non-Compliance Letter (NCL) was issued for not providing the annual electronic monitor certification, and the mechanical line leak detetcor tests. Liz Pelligrino of Discovery Tank Testing, Inc. will be notified.
01/26/1999 Legacy Activity Pinkovsky, Dennis D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed