DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/23/2021        Last Data Refresh: 04/22/2021        Report Generated from DOPPLER
 
Facility ID: 8506936
Facility Name: MOBIL-FT CAROLINE
 
05/18/2020 Enforcement Tracking Activity Collins, Megan
Activity Status: Open
05/15/2020 Enforcement Referral Activity Gainey, Helen
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 05/18/2020
Events:
Event Type: Activity has been assigned Date: 05/15/2020
Comment: Assigned to Megan Collins
Events:
Event Type: Activity has been submitted for approval Date: 05/15/2020
Comment: Submitted for approval by: Helen Gainey: Violations cited during 2/19/2020 compliance inspection.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 05/15/2020
Comment: Acknowledged and Assigned by Matthew J Harris
Events:
Event Type: Activity/Document was accepted on this date Date: 05/18/2020
Comment: Accepted by Megan Collins: ok
Events:
Event Type: Activity has been finished Date: 05/18/2020
Comment: Finished
Attachments:
Attachment Date: 05/15/2020 User: GAINEY_H_1
Description: 8506936_CRDE Information Sheet_5-15-2020
View Attachment
03/04/2020 Editable Letter Activity Mondo, Patrick W
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 03/04/2020
Comment: Sent
Events:
Event Type: Compliance Assistance Offer Verbal Date: 02/19/2020
Comment: Compliance Assistance Offer Verbal
Events:
Event Type: Activity has been finished Date: 03/04/2020
Comment: Finished
Attachments:
Attachment Date: 03/04/2020 User: MONDO_PW_1
Description: 8506936_CAO Letter_03-04-2020
View Attachment
02/19/2020 Violation Open Mondo, Patrick W
Significance: Minor Status: Open
Criteria ID: 4068
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1., 62-761.700(1)(a)2.
02/19/2020 Incident Activity Mondo, Patrick W
Activity Status: Open
02/19/2020 Site Inspection Activity Closed Mondo, Patrick W
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/19/2020
Activity Closed Date: 03/04/2020 Activity Closed By: MONDO_PW_1
Events:
Event Type: Activity has been finished Date: 03/04/2020
Comment: Finished
02/19/2020 Violation Open Mondo, Patrick W
Significance: SNC-B Status: Open
Criteria ID: 4016
Rule: 62-761.430(2)
02/19/2020 Violation Closed Mondo, Patrick W
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
10/11/2017 Editable Letter Activity Westerman, Michael L
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/11/2017
Comment: Finished
Attachments:
Attachment Date: 10/11/2017 User: WESTERMAN_ML_1
Description: Return to Compliance Letter
View Attachment
10/09/2017 Site Inspection Activity Closed Westerman, Michael L
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/09/2017
Activity Closed Date: 10/11/2017 Activity Closed By: WESTERMAN_ML_1
Events:
Event Type: Activity has been finished Date: 10/11/2017
Comment: Finished
06/23/2017 Editable Letter Activity Richards, Jean
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/23/2017
Comment: Finished
Attachments:
Attachment Date: 06/23/2017 User: RICHARDS_JE_1
Description: 8506936_CSNCL Viol 1105_06-23-2017
View Attachment
04/20/2017 Record Document Activity Richards, Jean
Activity Status: Closed
Contact Name: Johnny Shami Activity Closed Date: 07/04/2017
Events:
Event Type: Activity has been finished Date: 07/04/2017
Comment: Finished
03/06/2017 Violation Closed Cantu, Alisa B
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
03/06/2017 Electronic Communication Activity Cantu, Alisa B
Activity Closed Date: 03/06/2017 Activity Status: Closed
Date: 03/06/2017
Recipient: John Shami
Sender: Alisa Cantu
Subject: Inspection report
Message: Email of inspection report
Events:
Event Type: Activity has been finished Date: 03/06/2017
Comment: Finished
03/06/2017 Editable Letter Activity Cantu, Alisa B
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 03/07/2017
Comment: Submitted for approval by: Alisa B Cantu
Events:
Event Type: Activity has been finished Date: 03/07/2017
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 03/07/2017
Comment: Approved by Jean Richards: Approved
Attachments:
Attachment Date: 03/07/2017 User: RICHARDS_JE_1
Description: 8506936_1st County NCL Viol 1062_1105_1115_1117_1123_03-06-2017
View Attachment
03/03/2017 Violation Closed Cantu, Alisa B
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/03/2017 Violation Closed Cantu, Alisa B
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/02/2017 Violation Closed Cantu, Alisa B
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
03/02/2017 Violation Closed Cantu, Alisa B
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
03/02/2017 Violation Closed Cantu, Alisa B
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
02/28/2017 Attachment Cantu, Alisa B
02/28/2017 Electronic Communication Activity Cantu, Alisa B
Activity Closed Date: 02/28/2017 Activity Status: Closed
Date: 02/28/2017
Recipient: John Shami
Sender: Alisa Cantu
Subject: Pre-Inspection
Message: Email of pre-inspection report
Events:
Event Type: Activity has been finished Date: 02/28/2017
Comment: Finished
02/28/2017 Site Inspection Activity Closed Cantu, Alisa B
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/28/2017
Activity Closed Date: 03/06/2017 Activity Closed By: CANTU_AB_1
Events:
Event Type: Activity has not been approved Date: 03/05/2017
Comment: Not approved by Jean Richards: See comments on paper copy provided.
Events:
Event Type: Activity has been submitted for approval Date: 03/03/2017
Comment: Submitted for approval by: Alisa B Cantu
Events:
Event Type: Activity/Document has been approved Date: 03/06/2017
Comment: Approved by Jean Richards: Approved
Events:
Event Type: Activity has been submitted for approval Date: 03/06/2017
Comment: Submitted for approval by: Alisa B Cantu
Events:
Event Type: Activity has been finished Date: 03/06/2017
Comment: Finished
02/20/2015 Site Inspection Activity Closed Williams, April K.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/20/2015
Activity Closed Date: 02/20/2015 Activity Closed By: WILLIAMS_AK_1
Events:
Event Type: Activity has been finished Date: 02/20/2015
Comment: Finished
02/20/2015 Emergency Preparedness Information Activity Williams, April K.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/20/2015
Events:
Event Type: Activity has been finished Date: 02/20/2015
Comment: Finished
02/20/2015 Electronic Communication Activity Williams, April K.
Activity Closed Date: 02/20/2015 Activity Status: Closed
Date: 02/20/2015
Recipient: John Shami
Sender: EQD
Subject: Email - Compliance Report
Message: See Attachment
Events:
Event Type: Activity has been finished Date: 02/20/2015
Comment: Finished
11/16/2012 Electronic Communication Activity Korous, Eva
Activity Closed Date: 11/16/2012 Activity Status: Closed
Date: 11/16/2012
Recipient: John Shami
Sender: EQD
Subject: Report Email
Message: See attachment
Events:
Event Type: Activity has been finished Date: 11/16/2012
Comment: Finished
11/15/2012 Site Inspection Activity Closed Korous, Eva
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/15/2012
Activity Closed Date: 11/16/2012 Activity Closed By: KOROUS_E_1
Events:
Event Type: Activity has been finished Date: 11/16/2012
Comment: Finished
11/15/2012 Emergency Preparedness Information Activity Korous, Eva
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 11/16/2012
Events:
Event Type: Activity has been finished Date: 11/16/2012
Comment: Finished
06/07/2011 Site Inspection Activity Closed Borisade, Charles
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/07/2011
Activity Closed Date: 06/08/2011 Activity Closed By: BORISADE_KA_1
Events:
Event Type: Activity has been finished Date: 06/08/2011
Comment: Finished
06/07/2011 Emergency Preparedness Information Activity Borisade, Charles
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/07/2011
Events:
Event Type: Activity has been finished Date: 06/07/2011
Comment: Finished
03/01/2010 Attachment Holloway, Randall
02/24/2010 Issue Document Activity Towle, Michael
Activity Status: Closed
Contact Name: Towle Activity Closed Date: 03/01/2010
Events:
Event Type: Activity has been finished Date: 03/01/2010
Comment: Finished
02/22/2010 Issue Document Activity Towle, Michael
Activity Status: Closed
Contact Name: Towle Activity Closed Date: 02/22/2010
Events:
Event Type: Activity has been finished Date: 02/22/2010
Comment: Finished
02/19/2010 Site Inspection Activity Closed Towle, Michael
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/19/2010
Activity Closed Date: 02/22/2010 Activity Closed By: TOWLE_M
Events:
Event Type: Activity has been finished Date: 02/22/2010
Comment: Finished
02/05/2010 Issue Document Activity Towle, Michael
Activity Status: Closed
Contact Name: Towle Activity Closed Date: 02/08/2010
Events:
Event Type: Activity has been finished Date: 02/08/2010
Comment: Finished
12/21/2009 Site Inspection Activity Closed Holloway, Randall
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/21/2009
Activity Closed Date: 12/21/2009 Activity Closed By: HOLLOWAY_RW_1
Events:
Event Type: Activity has been finished Date: 12/21/2009
Comment: Finished
12/04/2009 Attachment Holloway, Randall
11/21/2008 Site Inspection Activity Closed Holloway, Randall
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/21/2008
Activity Closed Date: 11/24/2008 Activity Closed By: HOLLOWAY_RW_1
Comments:
Comment Date: 05/10/2009 User: HOLLOWAY_RW_1
Description: Proper notification given to Mr. Mike Hammock prior to inspection. Paper work inspection conducted on 5-15-09. Verified cover page information. Placard is current. Tank uses interstitial monitoring by sticking and monthly visual inspections for release detection. Piping and spill bucket use monthly visual inspections for release detection. No sumps or dispensers associated with this tank system.
11/21/2008 Emergency Preparedness Information Activity Holloway, Randall
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 11/24/2008
12/12/2007 Emergency Preparedness Information Activity Holloway, Randall
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/12/2007
12/07/2007 Site Inspection Activity Closed Holloway, Randall
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/07/2007
Activity Closed Date: 12/12/2007 Activity Closed By: HOLLOWAY_RW_1
Comments:
Comment Date: 02/01/2008 User: HOLLOWAY_RW_1
Description: Breach of Integrity test was performed by Fueling Components on 11-30-07. The tank passed the test. The next Breach of Integrity test is due by 11-30-2012. This facility is now in compliance.
02/20/2007 Attachment Holloway, Randall
02/20/2007 Attachment Holloway, Randall
02/20/2007 Attachment Holloway, Randall
02/20/2007 Attachment Holloway, Randall
02/15/2007 Site Inspection Activity Closed Holloway, Randall
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/15/2007
Activity Closed Date: 02/20/2007 Activity Closed By: HOLLOWAY_RW_1
Comments:
Comment Date: 01/23/2008 User: HOLLOWAY_RW_1
Description: 8 double sided dispensers on site. Maximum of 16 fueling positions.
02/07/2007 Emergency Preparedness Information Activity Holloway, Randall
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/07/2007
Comments:
Comment Date: 10/10/2007 User: HOLLOWAY_RW_1
Description: Proper notification given prior to inspection. Paperwork and physical inspection conducted on 10-11-07. Federal government facilities are exempt from Financial responsibility requirements. Annual placard is not required for federal government facilities. The tank and piping use interstitial monitoring for release detection. The tank is monitored by a Pneumercator and the piping and piping sump are monitored by monthly visual inspections of the piping sump. The Pneumercator also has a high level alarm for overfill protection. No evidence of a new release noticed during inspection. Fill is painted. Spill bucket dry and no cracks noticed. Piping sump dry and no cracks noticed. Tank and piping appear to be in good condition.
09/27/2006 Emergency Preparedness Information Activity Griffin, Tom
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/27/2006
Comments:
Comment Date: 09/06/2007 User: GRIFFIN_TW_1
Description: 8507168 HESS #09296 SYSTEM TEST SCHEDULE: GENERAL The method of release detection used at this facility is electronic interstitial monitoring of tank interstice & visual and electronic monitoring of sumps, spill/fill sumps & dispenser liners. The method of overfill protection used at this facility is flow shutoff. TANK Category B with continuous electronic monitoring ANNUAL LINE LEAK DETECTOR Line Leak Detector - 62-761.640(4) (a)/ (1103N): (Able to detect a 0.2 gph leak in the test mode/3 gph while in operation) Last: 1/20/2007 Due: 1/20/2008 ANNUAL OPERABILITY OF LEAK DETECTION DEVICES- 62-761.700(1) (c) 3 ATG: Veeder Root TLS 350 Last: 1/20/2007 Due: 1/20/2008 Tank Sensors: Last: 1/20/2007 Due: 1/20/2008 Interstitial Probe: Last: 1/20/2007 Due: 1/20/2008 Sump Probe: Last: 1/20/2007 Due: 1/20/2008 Fill/Spill Sensor: Last: 1/20/2007 Due: 1/20/2008 Dispenser Liner Probe: Last: 1/20/2007 Due: 1/20/2008
07/10/2006 Site Inspection Activity Closed Carroll, Albert
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/10/2006
Activity Closed Date: 07/12/2006 Activity Closed By: CARROLL_A
Comments:
Comment Date: 05/30/2007 User: SPEARS_CV_1
Description: 8625954_STARLINGS FUEL SERVICE, INC. CHAPTER 62-761 FAC: UNDERGROUND STORAGE TANK Miscellaneous Proper notification was given prior to the inspection and proper identification was presented to the facility responsible party upon entry to the premises. The method of release detection used at this facility is: Pneumercator TMS 3000-ATG-CSLD, line leak detectors, and visual inspections. The method of overfill protection used at this facility is: spill containment bucket, flow shut-off and level gauges/alarms. The site schematic has been reviewed for accuracy. The site equipment list has been reviewed for accuracy. The site photos have been reviewed for accuracy & relevancy. The facility coordinates in SWAP/Webpoint have been verified by office staff. Registration Registration Placard No: 270680 All systems are registered and match Placard (1001N): YES The Placard is current and the Registration fees paid (1002N): YES The Placard kept in view (1003N): YES Note: Registration Fees are due and payable no later than June 30 of each year. Financial Responsibility COMMERCE & INDUSTRY 4/18/2006 TO 4/18/2007 The Financial Responsibility Records were current and made available for review (1004B): YES, COMMERCE & INDUSTRY, effective 4/18/2007 expires 4/18/2008 A Certificate of Financial Responsibility was made available (1004B): YES Financial Responsibility must be renewed before 4/18/2008 and a new Certificate of Responsibility completed. Equipment Approvals/Alternate Procedure Equipment is approved by Department (2165N): YES Notification & Reporting The facility responsibility party has reviewed the information on screens 1/13 & 3/13 for accuracy. There is no information change requiring the submittal of a Registration Form. Performance Standards Category C Integral Pipe Category C system has a breach of integrity test (1020N): tanks installed 1/1/1999; test to be scheduled 2008. A monitoring point has been provided for secondary containment (1021N): YES Fill box or tank marked with color code or contents for Category C (1032N): YES Overfill provided that shuts off/restricts flow/alarms (1033B): YES Pressurized pipe has shear valve properly installed (1040N): YES Release Detection (See Note) A release can be detected from any portion of system: 600(a) (1)1 - (1058N): YES The release detection system is operational: 600(1) (a) 2 - (1059N): YES Release detection performed monthly: 600(1) (1) d - (1062B): YES Is mechanical leak detection system checked monthly: 600(1) (e) - (1063N): YES Is there interstitial monitoring for secondary containment? 600(1) (h) - (1066B): YES The RDRL/SPCC matches the release detection method: 640(1) (c) (1082N): YES Problems found during monthly visual inspections noted: 640(2) (e) ¿ (1091N): YES ATG system in test mode every 30 days or operated continuously - 640(3) (d) (1099N): YES Repairs Operation & Maintenance Piping sump - excess water or fuel removed (1115N): YES Release detection devices tested annually: 700(1) (3) c - (1117N): YES Recordkeeping Required records made available within five working days (1122N): YES Required records have been kept for 2 yrs (1123): YES Required records have been kept for the life of the system. (1124N): YES Incident & Discharge Response During the physical inspection of the facility, no evidence of a new product release was observed.
07/10/2006 Site Inspection Activity Closed Carroll, Albert
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/10/2006
Activity Closed Date: 07/12/2006 Activity Closed By: CARROLL_A
Comments:
Comment Date: 05/30/2007 User: SPEARS_CV_1
Description: 8625954_STARLINGS FUEL SERVICE, INC. CHAPTER 62-761 FAC: UNDERGROUND STORAGE TANK Miscellaneous Proper notification was given prior to the inspection and proper identification was presented to the facility responsible party upon entry to the premises. The method of release detection used at this facility is: Pneumercator TMS 3000-ATG-CSLD, line leak detectors, and visual inspections. The method of overfill protection used at this facility is: spill containment bucket, flow shut-off and level gauges/alarms. The site schematic has been reviewed for accuracy. The site equipment list has been reviewed for accuracy. The site photos have been reviewed for accuracy & relevancy. The facility coordinates in SWAP/Webpoint have been verified by office staff. Registration Registration Placard No: 270680 All systems are registered and match Placard (1001N): YES The Placard is current and the Registration fees paid (1002N): YES The Placard kept in view (1003N): YES Note: Registration Fees are due and payable no later than June 30 of each year. Financial Responsibility COMMERCE & INDUSTRY 4/18/2007 TO 4/18/2008 The Financial Responsibility Records were current and made available for review (1004B): YES, COMMERCE & INDUSTRY, effective 4/18/2007 expires 4/18/2008 A Certificate of Financial Responsibility was made available (1004B): YES Financial Responsibility must be renewed before 4/18/2008 and a new Certificate of Responsibility completed. Equipment Approvals/Alternate Procedure Equipment is approved by Department (2165N): YES Notification & Reporting The facility responsibility party has reviewed the information on screens 1/13 & 3/13 for accuracy. There is no information change requiring the submittal of a Registration Form. Performance Standards Category C Integral Pipe Category C system has a breach of integrity test (1020N): tanks installed 1/1/1999; test to be scheduled 2008. A monitoring point has been provided for secondary containment (1021N): YES Fill box or tank marked with color code or contents for Category C (1032N): YES Overfill provided that shuts off/restricts flow/alarms (1033B): YES Pressurized pipe has shear valve properly installed (1040N): YES Release Detection (See Note) A release can be detected from any portion of system: 600(a) (1)1 - (1058N): YES The release detection system is operational: 600(1) (a) 2 - (1059N): YES Release detection performed monthly: 600(1) (1) d - (1062B): YES Is mechanical leak detection system checked monthly: 600(1) (e) - (1063N): YES Is there interstitial monitoring for secondary containment? 600(1) (h) - (1066B): YES The RDRL/SPCC matches the release detection method: 640(1) (c) (1082N): YES Problems found during monthly visual inspections noted: 640(2) (e) ¿ (1091N): YES ATG system in test mode every 30 days or operated continuously - 640(3) (d) (1099N): YES Repairs Operation & Maintenance Piping sump - excess water or fuel removed (1115N): YES Release detection devices tested annually: 700(1) (3) c - (1117N): YES Recordkeeping Required records made available within five working days (1122N): YES Required records have been kept for 2 yrs (1123): YES Required records have been kept for the life of the system. (1124N): YES Incident & Discharge Response During the physical inspection of the facility, no evidence of a new product release was observed.
11/15/2005 Legacy Activity Allen, Eleanor
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/25/2004 Legacy Activity Torsanko, Grace
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/29/2003 Legacy Activity Torsanko, Grace
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
10/25/2003 Legacy Activity Torsanko, Grace
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/02/2003 Legacy Activity Dohaney, Tim
Activity Name: TANK COMPLIANCE - DISTRICT QA INSPECTION Activity Status: Closed
Completion Notes: QA INSPECTION FOR AUDIT.
02/15/2003 Legacy Activity Torsanko, Grace
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
05/15/2002 Legacy Activity Torsanko, Grace
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/23/2001 Legacy Activity Cummings, Constance C.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/22/2000 Legacy Activity Cummings, Constance C.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
05/20/1999 Legacy Activity Cummings, Constance C.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/17/1999 Legacy Activity Cummings, Constance C.
Activity Name: TANK CLOSURE INSPECTION Activity Status: Closed
Completion Notes: 500 GAL WASTE OIL TANK REMOVED